include: replace linux/module.h with "struct module" wherever possible
[linux-2.6/next.git] / Documentation / hwmon / adm1275
blob097b3ccc4be767fd02a8c205e09812ed8982c5d5
1 Kernel driver adm1275
2 =====================
4 Supported chips:
5   * Analog Devices ADM1275
6     Prefix: 'adm1275'
7     Addresses scanned: -
8     Datasheet: www.analog.com/static/imported-files/data_sheets/ADM1275.pdf
10 Author: Guenter Roeck <guenter.roeck@ericsson.com>
13 Description
14 -----------
16 This driver supports hardware montoring for Analog Devices ADM1275 Hot-Swap
17 Controller and Digital Power Monitor.
19 The ADM1275 is a hot-swap controller that allows a circuit board to be removed
20 from or inserted into a live backplane. It also features current and voltage
21 readback via an integrated 12-bit analog-to-digital converter (ADC), accessed
22 using a PMBus. interface.
24 The driver is a client driver to the core PMBus driver. Please see
25 Documentation/hwmon/pmbus for details on PMBus client drivers.
28 Usage Notes
29 -----------
31 This driver does not auto-detect devices. You will have to instantiate the
32 devices explicitly. Please see Documentation/i2c/instantiating-devices for
33 details.
36 Platform data support
37 ---------------------
39 The driver supports standard PMBus driver platform data. Please see
40 Documentation/hwmon/pmbus for details.
43 Sysfs entries
44 -------------
46 The following attributes are supported. Limits are read-write, history reset
47 attributes are write-only, all other attributes are read-only.
49 in1_label               "vin1" or "vout1" depending on chip variant and
50                         configuration.
51 in1_input               Measured voltage. From READ_VOUT register.
52 in1_min                 Minumum Voltage. From VOUT_UV_WARN_LIMIT register.
53 in1_max                 Maximum voltage. From VOUT_OV_WARN_LIMIT register.
54 in1_min_alarm           Voltage low alarm. From VOLTAGE_UV_WARNING status.
55 in1_max_alarm           Voltage high alarm. From VOLTAGE_OV_WARNING status.
56 in1_highest             Historical maximum voltage.
57 in1_reset_history       Write any value to reset history.
59 curr1_label             "iout1"
60 curr1_input             Measured current. From READ_IOUT register.
61 curr1_max               Maximum current. From IOUT_OC_WARN_LIMIT register.
62 curr1_max_alarm         Current high alarm. From IOUT_OC_WARN_LIMIT register.
63 curr1_highest           Historical maximum current.
64 curr1_reset_history     Write any value to reset history.